Section 5 Electrical System
5-1
Section 5
Electrical System
Electrical Sequence of Operation
Refrigerators - Self-Contained -
R1, R2, R3
For wiring diagram, see page 5-5
COOLING CYCLE
With the main ON/OFF switch in the ON
position, the current flows, energizing the
evaporator fan motors.
Current also flows through the closed contacts
of the temperature control, energizing the
condenser fan motor and the compressor.
OFF CYCLE
When the temperature control senses the
proper temperature, it opens, shutting off the
refrigeration system.
The refrigeration system remains off until the
temperature control senses approximately
38°F (3.3°C). (This also keeps the evaporator
defrosted.) At that time, the temperature
control closes and starts the refrigeration
system.
Refrigerators - Self-Contained -
RS1, RS2, RS3
For wiring diagram, see pages 5-6 and 5-7
COOLING CYCLE
With the main ON/OFF switch in the ON
position, the current flows, energizing the
evaporator fan motor(s).
Important
On early production RS1, RS2 and RS3
models, the evaporator fan motor(s) are
wired through the fan/light switch. Refer to
page 7-6 for modification instructions.
Current also flows through the closed contacts
of the temperature control, energizing the
condenser fan motor and the compressor.
OFF CYCLE
When the temperature control senses the
proper temperature, it opens, shutting off the
refrigeration system.
The refrigeration system remains off until the
temperature control senses approximately
38°F (3.3°C). (This also keeps the evaporator
defrosted.) At that time, the temperature
control closes and starts the refrigeration
system.